In order to develop a reliable tool for the maintenance planning of hydrogenerators, research works have been pursued to improve the immunity to noise of the "differential" technique of partial discharge measurements (PD). In this paper is presented 1) the "high-frequency grounding" technique that has been developed at IREQ to improve the signal-to-noise ratio of PD measurements systems and 2) the "time and amplitude" calibration technique that has been concurrently developed to achieve the low noise levels required for PD spectra measurements. Following the implementation on hydrogenerators of the HF grounding technique and of the enhanced calibration technique, noise-free PD spectra have been obtained. It is believed that these noise-free spectra will be more sensitive for the monitoring of the insulation conditions with time and for the detection of insulation defects at their early stages of development.
机译:为了开发用于氢化机构的维护规划的可靠工具,已经探讨了研究作品,以提高局部放电测量(PD)的“差分”技术的抗噪声。本文提出了1)“高频接地”技术,在ISERQ中开发,以提高PD测量系统的信噪比和2)已同时开发的“时间和幅度”校准技术为了实现PD谱测量所需的低噪声水平。在HF接地技术和增强校准技术的实施例的实施之后,已经获得了无噪声的PD谱。据信,这些无噪声光谱对于在其早期发育的早期监测绝缘条件和检测绝缘缺陷的情况下更敏感。