A Fault Line-Selection Method of Hybrid Cable-Overhead Line in Distribution Network Based on Morphology Filter and Hilbert-Huang Transform

机译:基于形态学滤波器和Hilbert-Huang变换的配电网混合电缆架空线断线选择方法

获取原文

摘要

While the hybrid transmission lines of distribution network occur the single line to ground faults, a fault line detecting method with HHT detective then compare the phase relation based on the phase relation of zero sequence current between fault line and unfault line is reverse. A morphological filter is first developed to filter noise in transient zero sequence currents. Applying HHT detective to define the fault time, then using the EMD to decompose the zero sequence current of 1/4 cycle after the fault happens and compare the mutate direction of highest frequency of IMF to identify the fault line. According to analyze the transient signals of distribution network occur the single line to ground faults, in the first 1/4 cycle after fault, the phase inversion is not happened and also can avoid the influence of CT saturation. The theoretic analysis and simulations indicate that the fault line detecting method is correct and reliable within the distribution network with overhead-cable mixed lines. In addition, HHT detective require the low hardware and easy to implement, so the method also has economical efficiency.
机译:虽然分配网络的混合传输线发生单行到接地故障,但是具有HHT侦探的故障线检测方法,然后基于故障线和触管线之间的零序电流的相位关系进行比较相位关系。首先开发一种形态过滤器以在瞬态零序电流中过滤噪声。应用HHT探测器定义故障时间,然后使用EMD在发生故障后分解1/4周期的零序电流,并比较IMF的最高频率的突变方向以识别故障线。根据分析分配网络的瞬态信号发生单线到接地故障,在故障后的第一个1/4循环中,不发生相位倒置,也可以避免CT饱和的影响。理论分析和模拟表明故障线检测方法在具有开销电缆混合线的分配网络中是正确可靠的。此外,HHT侦探要求低硬件且易于实现,因此该方法还具有经济效率。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号