Cross Texas Transmission (CTT) uses 345kV shunt reactors to regulate the high voltages during lightly loaded conditions on its long transmission lines spanning over 100 miles on a regular basis. Initially, the company experienced a few challenges during reactor energizations due to inrush conditions. As a result, CTT implemented a Digital Field Recorder (DFR) monitoring system to capture and examine inrush waveform conditions. Actual field data recorded from DFRs over a period of 14 months is analyzed to present and discuss the behavior of reactor switching due to inrush and other observed effects for different operating conditions. This paper has diverse, practical scenarios to offer in the form of waveforms during reactor energization which help understand and avoid misoperations.
机译:交叉德州传输(CTT)使用345kV并联反应器,在其长传输线上在跨越100英里的长传输线上在其长的速度条件下调节高电压。最初,由于涌入条件,该公司在反应堆通电期间经历了一些挑战。结果,CTT实现了一种数字字段记录器(DFR)监视系统,用于捕获和检查inrush波形条件。分析从DFR中记录的实际现场数据在14个月内呈现并讨论由于涌入和其他观察到的不同操作条件的效果而导致的反应器切换的行为。本文在反应堆通电期间以波形形式提供多样化,实际情况,有助于理解和避免误操作。