首页> 外文会议>Conference for Protective Relay Engineers >Impact of Inverter-based Resources on Impedance-based Protection Functions
【24h】

Impact of Inverter-based Resources on Impedance-based Protection Functions

机译:基于逆变器的资源对基于阻抗的保护功能的影响

获取原文

摘要

Inverter-based resources (IBRs) may inject nonconventional or no negative-sequence current during unbalanced faults. The adverse impact of such fault current characteristic has been reported on fault type identification and directional functions that are essential to impedance-based protection. However, the impact of IBR negative current injection on the core part of different implementations of impedance-based protection function has not been thoroughly investigated. Latest German Gird Code introduces a new requirement for IBRs to inject negative sequence current proportional to its measured negative sequence voltage. In this paper, we will investigate if this requirement can address challenges and issues raised by IBRs for protection relays. This paper investigates and compares the impact of IBRs with two options 1- no negative sequence current injection and 2- negative sequence current injection based on latest German code on phase comparator based methods and impedance-based protection functions. Theoretical analysis, software simulation and commercial relay test have been used for this investigation.
机译:在不平衡故障期间,基于逆变器的资源(IBR)可能注入非常规或无负序电流。据报道,这种故障电流特性对基于阻抗的保护所必需的故障类型识别和方向功能产生了不利影响。然而,IBR负电流注入对基于阻抗的保护功能的不同实现的核心部分的影响尚未得到彻底研究。最新的德国电网规范对IBRs提出了新的要求,要求IBRs注入与其测量的负序电压成比例的负序电流。在本文中,我们将调查这一要求是否能够解决IBRs提出的保护继电器的挑战和问题。本文研究并比较了IBRs与两种方案(1-无负序电流注入和2-基于最新德国规范的负序电流注入)对基于相位比较器的方法和基于阻抗的保护功能的影响。本研究采用了理论分析、软件模拟和商业继电器测试。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号