Detection of Inhibitor Content in Transformer Oil at Wavelengths below 1000 nm

机译:在1000nm以下的波长下检测变压器油中的抑制剂含量

获取原文

摘要

Power transformers are significant in the power transmission and distribution network. A continuous monitoring of the transformer is crucial in ensuring a longer life spend service of the transformer. This paper focuses on the characterization of transformer oil using optical detection method at wavelengths below 1000 nm, which can be detected using Silicon photodetector. Transformer oil samples with 5 different concentrations of inhibitor content were prepared for the optical characterization from 950 nm to 970 nm. The results of the experiment show an excellent correlation between the concentration of inhibitor content in the oil and the magnitude of the peak absorbance at the 959 nm wavelength. This approach can potentially lead to the development of low cost and portable device that can measure the concentration of inhibitor of the transformer oil.
机译:电力变电器在电力传输和配送网络中很大。在确保变压器的寿命较长的寿命方面,对变压器的连续监控至关重要。本文侧重于使用低于1000nm的波长的光学检测方法表征变压器油,这可以使用硅光电探测器检测。制备具有5种不同浓度抑制剂含量的变压器油样品,用于从950nm至970nm的光学表征。实验结果表明,油的抑制剂含量浓度与959nm波长的峰值吸光度的大小之间的优异相关性。这种方法可能导致能够测量变压器油抑制剂浓度的低成本和便携式设备的开发。