首页> 外文会议>IIR International congress of refrigeration >AN INTEGRATED CHILLER USING MAGNETIC-BEARING COMPRESSOR WITH THERMOSYPHON FOR YEAR-ROUND COOLING OF INTERNET DATA CENTRES: FEASIBILITY ANALYSIS
【24h】

AN INTEGRATED CHILLER USING MAGNETIC-BEARING COMPRESSOR WITH THERMOSYPHON FOR YEAR-ROUND COOLING OF INTERNET DATA CENTRES: FEASIBILITY ANALYSIS

机译:具有磁性轴承压缩机的集成冷却器,具有热源脊柱,用于全年冷却互联网数据中心:可行性分析

获取原文
获取外文期刊封面目录资料

摘要

Energy consumption for year-round cooling of Internet Data Centres (IDCs) is growing rapidly. In this study, an integrated air-cooled chiller, by adopting magnetic-bearing centrifugal compressor and sharing heat exchangers, is proposed to supply chilled water for IDCs. The integrated chiller can automatically work in three modes (vapour compression, mechanically driven heat pipe, and thermosyphon) according to ambient temperature. To analyze energy performance and feasibility of the chiller, an hourly energy consumption model is developed. Then, the energy performance of the integrated chiller located in four typical cities in north China (Harbin, Shenyang, Beijing, and Jinan) are investigated. Additionally, an economic analysis is also carried out. The results show that the energy saving effect is significant, especially in colder regions, and the proposed chiller is economically feasible.
机译:全年冷却互联网数据中心(IDC)的能源消耗迅速增长。在本研究中,提出了一种采用磁性离心压缩机和共用热交换器的集成风冷冷却器,以供应IDC的冷水。根据环境温度,集成的冷却器可以自动以三种模式(蒸汽压缩,机械驱动的热管和热循环)工作。为了分析冷却器的能量性能和可行性,开发了一小时的能耗模型。然后,调查了位于华北四个典型城市(哈尔滨,沉阳,北京和济南)的集成冷却器的能量性能。此外,还进行了经济分析。结果表明,节能效果显着,特别是在较冷的地区,所提出的冷却器在经济上是可行的。