摘要

The pumped loop heat pipe heat exchanger unit for cooling consumes low power and has a high coefficient of performance (EER). For optimization applications at small data centers, this paper investigated the operating performance of the pumped loop heat pipe heat exchanger unit used in a small data center. The EER under different outdoor temperatures was analyzed, and the fitted operating characteristic curve showed that EER varied with outdoor temperature. An energy saving analysis was done with the fitting curve, and the total energy consumption was calculated at each temperature interval in Beijing. The results show that in transitional and winter season, when the outdoor temperature is below 15°C, the pumped loop heat pipe heat exchanger unit can be turned on to bear part or total thermal load and performs well in energy saving. Compared to the air conditioning and refrigeration system for cooling, the energy saving can reach at least 35.76%.
机译:用于冷却的泵送回路热管热交换器单元消耗低功率并具有高度的性能系数(eer)。对于小型数据中心的优化应用,本文研究了在小型数据中心的泵送回路热管热交换器单元的运行性能。分析了不同户外温度下的eer,配合的操作特性曲线显示eer随着室外温度而变化。用拟合曲线进行节能分析,并在北京的每个温度间隔计算总能量消耗。结果表明,在过渡和冬季,当室外温度低于15°C时,泵送环热管热交换器单元可以接通,以承受部分或全热负荷,并在节能中执行良好。与空调和冷藏系统进行冷却相比,节能可达到至少35.76%。