Equivalent grid impedance is an important information for testing control stability of grid-connected inverters. Furthermore, grid impedance parameters impact on local grid voltage when the local load or generator changes its active and reactive power. In grid connection standards such as the Brazilian Association of Technical Standards (ABNT) Brazilian Regulatory Standard (NBR) 16149, Photovoltaic (PV) inverters higher than 6 kW shall have external control of active and reactive power. This manuscript proposes a methodology for experimental determination of grid impedance by using the external commands of PV inverters. Experimental results were obtained with a 100 kW inverter of a photovoltaic power plant, and then the local grid impedance was calculated. Finally, the impedance calculation was validated in simulation.
机译:等效网格阻抗是用于测试网格连接逆变器的控制稳定性的重要信息。此外,当局部负载或发电机改变其主动和无功功率时,网格阻抗参数对本地电网电压的影响。在网格连接标准,如巴西技术标准(ABNT)巴西调节标准(NBR)16149,高于6 kW的光伏(PV)逆变器应具有主动和无功功率的外部控制。该稿件通过使用PV逆变器的外部命令提出了一种方法来实验确定电网阻抗的方法。用100 kW逆变器的光伏电厂获得实验结果,然后计算局部电网阻抗。最后,在模拟中验证了阻抗计算。