首页> 外文会议>IEEE Brazilian Power Electronics Conference >Control of weighted average current of Voltage sourced Inverters with LCL-filter for grid connected applications
【24h】

Control of weighted average current of Voltage sourced Inverters with LCL-filter for grid connected applications

机译:用LCL过滤器控制电压源逆变器的加权平均电流,用于网格连接应用

获取原文

摘要

This paper proposes the use of an alternative current control strategy for grid connected Voltage Source Inverters (VSIs) via LCL-filters. In this strategy, the weighted average current flowing through the LCL-filter inductors is used as a control variable, droping the order of the plant transfer function, from three to one, similar to the obtained from an L-filter. A Model Reference Control (MRC) is used for reference tracking in short circuit, while an Adaptive Feedforward cancellation scheme (AFC) is used to compensate for the voltage disturbances effect at the point of commom coupling with the grid.
机译:本文提出了通过LCL-滤波器对网格连接电压源反相器(VSIS)的替代电流控制策略使用。在该策略中,流过LCL滤波器电感器的加权平均电流用作控制变量,将植物传递函数的顺序从三到一个丢弃,类似于从L滤波器获得的。模型参考控制(MRC)用于短路中的参考跟踪,而自适应前馈取消方案(AFC)用于补偿与网格的结交点处的电压干扰效应。