首页> 外文会议>ASME International Heat Transfer Conference >EXPERIMENTAL INVESTIGATION ON THE PLATE HEAT PIPE HEAT EXCHANGER FOR HEAT RECOVERY CHARACTERISTIC IN ROOM VENTILATION
【24h】

EXPERIMENTAL INVESTIGATION ON THE PLATE HEAT PIPE HEAT EXCHANGER FOR HEAT RECOVERY CHARACTERISTIC IN ROOM VENTILATION

机译:室内通风中热回收特性板热管换热器的实验研究

获取原文

摘要

A plate HPHE (heat pipe heat exchanger) has been designed and constructed for heat recovery in this paper. The plate HPHE is constituted by plate heat pipes with microchannels. Many parameters affect the performance of the HPHE. In this paper, the effect of three parameters: inlet air temperature (27-40°C), working fluid (methanol, acetone, R113, R141b), and heat exchange area (single layer, double layer) were investigated experimentally. The overall experiments were carried out under the simulated summer condition, the vacuum of the HPHE was set at 1×10~(-3)Pa, and the filling ratio was 1/3. The air volume rates were changed from 60, 90, 120 and 150 m~3/h. The fresh air temperature varied from 27 to 40°C, whereas the return air temperature was kept at about 24°C. The results show that, at the same air volume, the effectiveness increases with increase of the inlet temperature of fresh air. The effectiveness of HPHE_d with R141b as working fluid is superior to R113, acetone and methanol, and the maximum effectiveness reaches to 58%. The effectiveness of the HPHE of single layer is lower than that of double layer by about 6%-18% at the temperature from 29 to 40°C.
机译:在本文中设计和构造了板HPHE(热管式热交换器)以进行热回收。板HPHE由带有微通道的板热管构成。许多参数会影响HPHE的性能。本文研究了三个参数:入口空气温度(27-40°C),工作流体(甲醇,丙酮,R113,R141B)和热交换区域(单层,双层)进行了实验。在模拟夏季条件下进行整体实验,将HPHE的真空设定为1×10〜(3)PA,填充率为1/3。空气量率从60,90,120和150m〜3更换。新的空气温度从27〜40℃变化,而返回空气温度保持在约24℃。结果表明,在相同的空气量,有效性随着清新空气的入口温度的增加而增加。 HPHE_D与R141B作为工作流体的有效性优于R113,丙酮和甲醇,最大效果达到58%。单层HPHE的有效性低于29至40℃的温度下的双层的约6%-18%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号