This study investigates the performance of an NH{sub}3/CO{sub}2 cascade system for supermarket refrigeration application in a laboratory environment. The tested CO{sub}2 system is designed and scaled to fulfill the requirements of an average size supermarket in Sweden. Possibility for hot gas defrost in the freezers has been investigated and compared to the conventional electric heaters defrost method. Two cascade condenser arrangements have been evaluated. The cascade system has been compared to R404A system installed in the same laboratory. The results show that connecting the cascade condenser via thermosyphon or hot gas de-superheat arrangements yields good system stability and heat transfer performance. Hot gas defrost successfully defrosted the freezer evaporator but with long period and higher energy consumption compared to the conventional electric defrost method. The tested cascade system had up to 60% higher total COP compared to the R404A system installed in laboratory.
机译:本研究调查了在实验室环境中的超市制冷应用的NH {Sub} 3 / Co {Sub} 2级联系统的性能。测试和扩展测试的CO {Sub} 2系统以满足瑞典平均超市的要求。已经研究了冷冻机中的热气除霜的可能性,并与传统的电加热器除霜方法进行了比较。已经评估了两个级联冷凝器布置。将级联系统与安装在同一实验室中的R404A系统进行比较。结果表明,通过热辛磷酸盐或热气体去除过热装置连接级联冷凝器产生良好的系统稳定性和传热性能。热气体除霜成功地改装了冷冻机蒸发器,但与传统的电解除霜方法相比,长期长时间和更高的能耗。与安装在实验室中安装的R404A系统相比,测试的级联系统总共高达60%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号