首页> 外文会议>International Conference on Indoor Air Quality and Climate >DRAFT SENSATION STUDY IN A SPACE SERVED BY DISPLACEMENT VENTILATION SYSTEM IN THE TROPICS
【24h】

DRAFT SENSATION STUDY IN A SPACE SERVED BY DISPLACEMENT VENTILATION SYSTEM IN THE TROPICS

机译:热带位移通风系统服务的空间中的感觉研究

获取原文

摘要

This paper presents a draft perception study of Displacement Ventilation (DV) system in a Field Environmental Chamber (FEC) with tropically acclimatized subjects. A total of 60 subjects, 30 males and 30 females, were exposed to 3 vertical air temperature gradients, 1, 3 & 5 K/m, between 0.1 and 1.1 rn heights and 3 room air temperatures, 20, 23 & 26°C at 0.6 m height for a 3-hour period. Air velocity near the subjects was maintained at below 0.2 m/s. Relative Humidity (RH) at 0.6 m height and fresh air provision was fixed at 50% and 10 l/s/p respectively. It was found that in the space served by DV system, draft perception was insignificantly affected by temperature gradient. Room air temperature had greater impact on percentage dissatisfied due to air movement than temperature gradient. Cold sensation would add draft risk and warm sensation would increase percentage dissatisfied due to insufficient air movement.
机译:本文介绍了具有热度适应对象的现场环境室(FEC)中位移通风(DV)系统的感知研究草案。共有60项受试者,30名男性和30名女性,暴露于3个垂直的空气温度梯度,1,3&5 k / m,在0.1和1.1 rn高度,3室空气温度,20,23℃,23°C之间0.6米高,3小时内。受试者附近的空气速度保持在0.2米/米以下。在0.6μm的相对湿度(RH),高度和新鲜空气供应分别固定在50%和10L / s / p处。发现在DV系统服务的空间中,感知草案受到温度梯度的微不足道的影响。房间空气温度对由于空气运动而不是温度梯度而产生的百分比对不满意的百分比。感冒感应增加风险草稿,温暖的感觉会增加由于空气运动不足而不满意的百分比。