VENTILATION RATES IN U.S. OFFICE BUILDINGS FROM THE EPA BASE STUDY

机译:美国EPA基础研究中的美国办公楼的通风率

获取原文

摘要

The EPA BASE study involved indoor environmental measurements in 100 U.S. office buildings. This paper presents an analysis of the measured outdoor air ventilation rates, including comparisons with the requirements in ASHRAE Standard 62. The outdoor ventilation rates measured using duct traverses at the air handler intakes are higher than might be expected, with a mean value of about 55 L/s per person. However, these elevated values are not so unexpected given the low occupant density (mean of about 4 persons per 100 m{sup}2) and the high outdoor air fractions (mean of about 35%). Air change rates based on peak carbon dioxide concentrations in the space are lower than the volumetric values with a mean of about 20 L/s per person. Questions exist regarding the reliability of these peak CO{sub}2 values based on the validity of the assumptions on which the determinations are based.
机译:EPA基础研究涉及100个U. Office建筑物的室内环境测量。本文提出了对测量的室外空气通风率的分析,包括与ASHRAE标准62中的要求的比较。使用管道进气口的导管横穿测量的室外通风率高于预期,平均值约为55每人l / s。然而,对于低乘员密度(每100 m {sup} 2的平均值为约4人)和高室外空气馏分(平均值约为35%),这些升高的值并不是如此意外。基于空间中的峰值二氧化碳浓度的空气变化率低于每人约20升/秒的体积值。基于确定所基于的假设的有效性,存在关于这些峰值CO {sub} 2值的可靠性的问题。