摘要

In order to solve the problem of single phase grounding fault locating in non-effectively grounding network, this paper analyzes the character of single phase grounding fault. According to the working principle of generating line insulation supervisory devices in transformer substation, the property of line imbalance voltage, and the practical operation demand of feeder terminal unit (FTU), a method of single phase grounding fault locating for FTU, the time limit & zero-sequence voltage method, is proposed, which operates on the feeder automation system of voltage-time type. The main principle about this method is given and the operating mode how to cooperate FTU is also discussed. At last, combined with the project example of Zhongshan loop-feeder automation system, the analysis about fault insulating process is described in detail. It is pointed out that the time limit & zero-sequence voltage method is feasible and practical.
机译:为了解决在非有效接地网络中定位单相接地故障的问题,本文分析了单相接地故障的特征。根据变电站的生产线绝缘监控器件的工作原理,线路不平衡电压的性质,以及馈线终端单元(FTU)的实际运行需求,一种用于FTU的单相接地故障的方法,时间限制&提出零序电压法,其在电压时型进料器自动化系统上运行。关于该方法的主要原理,还讨论了如何合作FTU的操作模式。最后,结合中山环路馈线自动化系统的项目示例,详细描述了关于故障绝缘过程的分析。指出,时间限制和零序电压方法是可行和实用的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号