Harmonics and PQ Events Monitoring in an Electrified Metro-Transit System

机译:谐波和PQ事件在电气化的地铁交通系统中监测

获取原文

摘要

The paper illustrates some results of a wide power quality (PQ) survey performed on the power supply insinuations of the metro-transit system serving the city of Rome, in Italy, The system currently includes two railway lines supplied at 1,500 V DC through several AC/DC 3.7 MW rated converters. The power supply of the system is provided at medium voltage (20 kV) from five different connections to the public grid. Fourteen electrical substations provide the total demand of about 20 MW of the system. The survey, currently still in progress, involves monitoring activities aimed at identifying possible PQ problems of various nature. Identification of typical daily patterns of harmonics distortion due to the system is even a task of the current survey.
机译:本文说明了在意大利服务城市罗马城市的电力供应系统的宽电力质量(PQ)调查的一些结果,该系统目前包括在1,500 V DC的两条铁路线通过几种AC提供/ DC 3.7 MW额定转换器。系统的电源以与公共网格的五个不同连接的中电压(20kV)提供。十四个电气变电站提供了大约20 mW的系统。目前正在进行的调查涉及监测旨在确定各种性质可能的PQ问题的活动。识别由于系统引起的谐波畸变的典型日常模式甚至是当前调查的任务。