首页> 外文会议>International Conference on Harmonics and Quality of Power >A Contribution to Establish Proceedings for Quantification of Voltage Harmonic Distortion in Commercial Buildings
【24h】

A Contribution to Establish Proceedings for Quantification of Voltage Harmonic Distortion in Commercial Buildings

机译:建立商业建筑中电压谐波变形的程序的贡献

获取原文

摘要

This article presents the results of measuring made in business buildings in a range of 1 up to 24 days. The statistic treatment of the data allows the establishment of a typical period that best characterizes the harmonic distortions in a given building. Moreover, it evaluates some points as choosing one phase to represent the others. The frequency of measurement is also one topic of the analyses. Following all the data collected was evaluated based by the limits proposed by international standards: IEEE, European and Brazilian Recommendation. Based on these analyses, this article concludes that, for commercial charges, measures made from 2:00pm up to 6:00pm in a typical day and spaced by 15 minutes are sufficient for quantifying the voltage harmonic distortions. Although these results may not be immediately applied for other kinds of charges, the methodology presented in this article can be useful for companies and professionals interested in the quantification and the qualification of the harmonic distortion of voltage and current.
机译:本文介绍了在14天内的商业建筑中衡量的结果。数据的统计治疗允许建立一个典型的时期,最能表征给定建筑物中的谐波扭曲。此外,它评估一些点作为选择一个阶段来代表其他阶段。测量频率也是分析的一个主题。根据国际标准提出的限制,根据国际标准提出的限制进行了遵循所在的所有数据:IEEE,欧洲和巴西建议。基于这些分析,本文得出结论,对于商业费用,在典型的一天下午2:00至下午6:00至下午6:00和15分钟间隔15分钟的措施足以量化电压谐波扭曲。虽然这些结果可能无法立即申请其他类型的费用,但本文提出的方法可能对对量化感兴趣的公司和专业人士以及电压和电流的谐波失真的资格有用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号