Resistance to ground of body on non homogeneous soil

机译:非均匀土壤抗身地面

获取原文

摘要

To reduce touch voltage and step voltage in the case of a fault in HV systems, one of the following methods is generally used: the installation of additional earth electrodes to provide potential grading on the ground surface or the soil insulation by means of a high resistance layer. The protective method using the insulating layer reduces the touch and step voltages depending on the resistivity of the layer and on the resistivity of the soil. This paper concerns with the evaluation of the resistance to earth of body (REB) for different insulating layer placed on homogeneous and non-homogeneous ground. The calculation of the RB and the evaluation of the voltage on the surface of the earth have been carried out with analytical methods and with experimental tests on a scale model. Other experimental measures have been carried out to determinate the resistivity of different insulating layers as asphalt, rock, concrete etc.
机译:为了降低HV系统故障的情况下的触摸电压和阶跃电压,通常使用以下方法之一:通过高电阻安装额外的接地电极以提供地面或土壤绝缘的潜在分级层。使用绝缘层的保护方法根据层的电阻率和土壤的电阻率降低触摸和阶跃电压。本文涉及对均匀和非均匀地上的不同绝缘层的对身体(REB)的抗性的评估。 RB的计算和地球表面上电压的评估已经通过分析方法进行,并在比例模型上进行实验测试。已经进行了其他实验措施,以确定不同绝缘层的电阻率作为沥青,岩石,混凝土等。