The Kii channel HVDC transmission system (1400 MW in the first stage) was commissioned in the year 2000 and transmits power generated in Shikoku Island to the AC 500 kV system on Honshu Island. The transmission line of approximately 100 km between the converter stations consists of two sections-undersea cable and overhead line sections. The transmission lines consist of 2 main lines and 2 return lines. The fault protection function was verified by making artificial grounding faults both for the main lines and return lines during a series of commissioning tests. The characteristics of the protection system of the return circuit including the metallic return transfer breakers (MRTBs) were evaluated from the tests. At some of the points along the line, the grounding arc extinguishes itself before closing MRTB and at other points; the, grounding arc is cleared by closing MRTB. It was confirmed that the clearing time of the grounding arc was consistent with the system design parameters.
机译:KII通道HVDC传输系统(第一阶段1400 MW)于2000年进行委托,并在绍洛库岛生成的电力传输到Honshu岛的AC 500 KV系统。转换器站之间大约100 km的传输线由两个部分 - 下端电缆和架空线部分组成。传输线由2条主线和2个返回线组成。故障保护功能通过在一系列调试测试期间的主线和返回线路进行人工接地故障来验证。从测试中评估包括金属回流转移断路器(MRTB)的返回电路的保护系统的特性。在沿线的一些点,接地弧线在关闭MRTB和其他点之前熄灭;通过关闭MRTB清除,接地电弧。确认接地弧的清除时间与系统设计参数一致。