In this paper an attempt is made to verify the permissible upper limit (U{sub}s= 50 mV) of the voltage drop across a low voltage stationary contact in accordance with VDE 0660. A mathematical relation is proposed for the voltage drop, U{sub}s, across a low voltage stationary contact dependent on the temperature. U{sub}s = 50 mV is considered as a relevant value for evaluation of the temperature rise, because it represents the permissible upper limit of the voltage drop across a low voltage stationary contact in accordance with VDE 0660. The results of experiments carried out agree closely with the calculations of the temperature rise, which have been evaluated using the above mentioned upper limit.
机译:在本文中,尝试根据VDE 0660验证电压降低电压降的允许上限(U {Sub} S = 50 mV)。提出了用于电压降的数学关系,U. {sub} s,跨越低压静止接触,取决于温度。 u {sub} s = 50 mv被认为是用于评估温度升高的相关值,因为它表示根据VDE 0660的低压静止接触电压降的允许上限。实验结果进行了与使用上述上限进行评估的温度升高的计算密切合同。