首页> 外文会议>International Telecommunications Energy Special Conference >Low energy air conditioning of shelters for telecommunication networks
【24h】

Low energy air conditioning of shelters for telecommunication networks

机译:电信网络避难所能量空调

获取原文

摘要

The control of the air temperature in a shelter for telecommunication networks is an important task for the correct operation of its electronic equipment. Different technical solutions have been studied in order to improve the energy performances of air conditioning plants: for this purpose direct free cooling allows to reduce the energy consumption to maintain the internal air temperature below the prescribed values. Nowadays the internal air temperature may rise up to 60°C, due to the high technology of the electronic equipment, and new solutions for the air temperature control can be proposed. This paper analyses the dynamic thermal performances of a shelter used in telecommunication networks, fitted up with an "air - to air" plate heat exchanger without mixing between internal and external air flows. Useful information, concerning the thermal and energy performances of this system is given for design purposes.
机译:用于电信网络的避难所中的空气温度控制是其电子设备正确操作的重要任务。已经研究了不同的技术解决方案,以改善空调厂的能量性能:为此目的,直接自由冷却允许降低能量消耗,以保持低于规定值的内部空气温度。如今,由于电子设备的高技术,内部空气温度可高达60°C,并且可以提出用于空气温度控制的新解决方案。本文分析了电信网络中使用的避难所的动态热性能,安装在内部和外部空气流之间的“空气 - 空气”板式换热器中,不混合。有关该系统的热量和能量性能的有用信息被提供设计目的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号