Power quality investigation of cluster of phase controlled rectifiers of airport grounding lighting system

机译:机场接地照明系统相控整体集群的电能质量调查

获取原文

摘要

Single phase thyristor rectifiers are widely used in modern airports as DC power supply for such loads as air-conditioners, communication, computers and airport grounding lighting system (AGL). The disadvantages of this kind of rectifier are the waveform distortion and the unbalance of loading, both of which have become a concern at many airports. In this paper, the harmonics produced by clusters of phase controlled rectifiers of an airport grounding lighting system are studied based on experimental measurement. It is shown that these rectifiers are the dominant harmonics source of the airport electrical power system. Harmonic pollution is found to be closely related to the load level of the airport grounding lighting system. Voltage waveform distortion at the point of common coupling (PCC) is primarily a result of harmonic current generated by the power electronics controlled loads. It is also found that total voltage harmonics distortion does not necessarily increase with the increase of current distortion at PCC. The harmonics and unbalance for combined loads are also investigated in this paper. Severe unbalance is observed which is disadvantageous for the power transformer and the auxiliary generator.
机译:单相可控硅整流器被广泛用于现代机场作为用于这样的负载如空调机,通信,计算机和机场接地照明系统(AGL)的直流电源。这种整流器的缺点是波形失真和负载的不平衡,这两者已经成为许多机场的担忧。在本文中,由机场接地照明系统的相控整流器的簇中产生的谐波进行了研究基于实验测量。结果表明,这些整流器是机场电力系统的主导谐波源。谐波污染被发现是密切相关的机场接照明系统的负荷水平。在公共耦合(PCC)的点的电压波形失真是主要由控制的负载功率电子器件产生的谐波电流的结果。它也发现,总电压谐波失真不一定与在PCC的电流失真的增加而增加。联合载荷的谐波和不平衡也研究了本文。严重不平衡观察到,这是不利的电源变压器和辅助发电机。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号