首页> 外文会议>International Symposium on High-voltage engineering >Acoustic partial discharge measurements for transformer insulation-an experimental validation
【24h】

Acoustic partial discharge measurements for transformer insulation-an experimental validation

机译:变压器绝缘的声学局部放电测量 - 实验验证

获取原文

摘要

Acoustic partial discharge (PD) measurement is a useful method of identifying and locating PD in a power transformer in service. In this paper an experimental validation has been performed on a transformer insulation model using an acoustic PD detector. While the efficacy of the method is proved, it is observed that the signal gets attenuated significantly when it passes through pressboard barriers. Even though acoustic PD values can be correlated with the maximum discharge magnitude for a single discharge activity in the laboratory simulations, this relationship could not be established during actual PD measurements in a transformer at site, as the acoustic PD signal depends upon many factors.
机译:声学局部放电(PD)测量是在服务中的电力变压器中识别和定位PD的有用方法。本文在使用声学PD检测器对变压器绝缘模型进行了实验验证。虽然证明了该方法的功效,但观察到当通过压板屏障时,信号显着衰减。即使声学PD值可以与实验室模拟中的单个放电活动的最大放电幅度相关,但由于声学PD信号取决于许多因素,因此不能在现场变压器中的实际PD测量期间建立这种关系。