首页> 外文会议>International Symposium on High-voltage engineering >Effect of mechanical pressure and silicone grease on partial discharge characteristics for model XLPE transmission cable joint
【24h】

Effect of mechanical pressure and silicone grease on partial discharge characteristics for model XLPE transmission cable joint

机译:机械压力和硅润滑脂对XLPE传输电缆接头模型局部放电特性的影响

获取原文

摘要

This paper reports on the effects of mechanical pressure and silicone grease on the partial discharge (PD) characteristics at EPR-epoxy interfaces in model cable joints. An ultra wide band PD detection system was used. The PD parameters investigated are: rise time, width, fall time, amplitude, inception voltage and frequency of pulses. PD can cause degradation and eventually lead to breakdown. The presence of air bubbles or contaminants at interfaces enhances the local electric field and initiate PD. The effectiveness of mechanical pressure and/or silicone grease to reduce PD activity was demonstrated.
机译:本文报道了机械压力和硅润滑脂对模型电缆接头中EPR-环氧界面处的局部放电(PD)特性的影响。使用超宽带PD检测系统。研究的PD参数是:上升时间,宽度,下降时间,幅度,脉冲的初始电压和频率。 PD可能导致劣化,最终导致故障。界面处的气泡或污染物的存在增强了局部电场并引发PD。证明了机械压力和/或硅氧烷润滑脂减少PD活性的有效性。