DSP implementation of output voltage reconstruction in CSI based UPS systems

机译:基于CSI的UPS系统输出电压重建的DSP实现

获取原文

摘要

Current source inverter-based uninterruptible power supplies (UPS) require sensing of two or more output voltages and synchronization with the AC input voltage in addition to the DC voltage sensors used for protection purposes. This paper proposes a DSP-based space vector control scheme that requires only information provided by the DC bus sensors. Output voltage estimation is based on AC line voltage reconstruction by means of information available on the DC bus and knowledge of the PWM pattern. In addition to providing low output voltage harmonic distortion, the system minimizes the component count and therefore increases ruggedness. The paper presents the DSP algorithms required for the operation of the system, and experimental results on a 208 V, 60 Hz, 5 kVA prototype inverter.
机译:除了用于保护目的的直流电压传感器之外,电流源基于逆变器的不间断电源(UPS)还需要感测两个或多个输出电压和与AC输入电压同步。本文提出了一种基于DSP的空间矢量控制方案,其仅需要DC总线传感器提供的信息。输出电压估计基于通过在DC总线上可用的信息和PWM模式的知识提供交流线电压重建。除了提供低输出电压谐波失真之外,系统还最大限度地减少了组件计数,因此增加了坚固性。本文介绍了系统运行所需的DSP算法,以及208 V,60 Hz,5 kVA原型逆变器的实验结果。