The research of arc-proofness of set tools for 110-220 kV live line works

机译:110-220 KV Live Line工程套装电弧耐电压的研究

获取原文

摘要

This paper presents the results of studies on the arc-proofness of insulating booms of aerial platforms for live line works. The data obtained with 5-20 kA power arcs applied for 1.5-0.1 sec, show acceptable arc-proofness of tested insulating boom samples and full-scale models as well as their ability to withstand nominal voltage or even switching overvoltages after such an arc, if autoreclosing occurs during live line work. The obtained results make possible further improvements of existing telescopic platforms.
机译:本文介绍了对现场生产线的空中平台绝缘臂的耐弧度的研究结果。使用5-20 ka电弧获得的数据施加1.5-0.1秒,显示了测试的绝缘动力样本和全尺寸模型的可接受的灭弧性,以及它们在弧形之后耐受标称电压甚至在过电压的能力,如果在实时运行过程中发生自动流。获得的结果可以进一步改进现有的伸缩平台。