During the 2005 National Electrical Code (NEC) review cycle, a relatively simple revision was made that will have a significant impact on the cathodic protection systems of petroleum and chemical facilities (plants) in the future. The 2005 NEC now makes it clear that there must be an interconnection of all concrete-encased steel reinforcing bar (rebar) to the facility grounding electrode system. For facilities using copper grounding electrode systems and also having cathodic protection as part of their corrosion mitigation and integrity programs, this revision may require a facility to change their entire cathodic protection design and operating philosophy. It will definitely require greater coordination and cooperation between the various engineering and construction disciplines. This paper will discuss some of the technical aspects of this grounding requirement and build a case for the cathodic protection philosophy that the authors believe will be necessary to comply with both NEC and process safety management program requirements.
机译:在2005年国家电气规范(NEC)审查周期中,制定了一个相对简单的修订,这将对未来石油和化学设施(植物)的阴极保护系统产生重大影响。 2005年NEC现在明确表示,必须将所有混凝土钢加强杆(钢筋)互连到设施接地电极系统。对于使用铜接地电极系统的设施以及作为其腐蚀缓解和完整性方案的一部分的设施,这种修订可能需要设施来改变整个阴极保护设计和操作理念。它肯定需要各种工程和施工学科之间更大的协调与合作。本文将讨论此接地要求的一些技术方面,并为作者认为将需要遵守NEC和流程安全管理方案要求,建立一个阴极保护哲学的案例。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号