首页> 外文会议>International Conference on Properties and Applications of Properties and Applications of Dielectric Materials >Selection of insulation level of HVAC power lines operating in high altitude polluted area
【24h】

Selection of insulation level of HVAC power lines operating in high altitude polluted area

机译:高海拔污染区域运行HVAC电力线绝缘水平的选择

获取原文

摘要

A description is given of a method for choosing the insulation level of power lines operating in a high-altitude polluted area on the basis of an artificial pollution test. The test was carried out in a pressure chamber in which the air pressure could be controlled. The chamber was used to simulate air pressure for different altitudes. It was found that under the same degree of pollution the withstand voltage of insulators decreased as the altitude increased. For several kinds of test insulator, the withstand voltage was higher as the creepage distance is increased. The shape of the shed affects the withstand voltage. On the basis of the test results, recommendations are made for choosing insulation for lines operating in high-altitude polluted areas.
机译:给出了基于人工污染测试选择在高空污染区域中操作的电力线绝缘水平的方法。测试在压力室中进行,其中可以控制空气压力。腔室用于模拟不同高度的气压。发现,随着海拔高度增加,在相同程度的污染程度下,绝缘体的耐压降低。对于几种测试绝缘体,随着爬电距离的增加,耐压较高。 SHED的形状会影响耐压。在测试结果的基础上,建议采用在高海拔污染区域中运行的线路的绝缘保温。