Partial discharges in transformer oil

机译:变压器油中的部分放电

获取原文

摘要

Since a long time the existence of Partial discharges (PD) in transformer oil was doubted because breakdown and inception levels are very close. This confirms the presently accepted fact that [1] PD occur in oil. In the breakdown process the formation of a “bubble” or “cavity” is accepted generally as a part of the initiatory process. When the bubble reaches a “critical size” a discharge occurs [2]. When such a discharge occurs it can be shown that the bubble can grow in size leading to second discharge which grows to a breakdown. If it bursts into smaller sizes the discharge stops [3,4]. The probability of this is very low.
机译:自从很长一段时间以来,反感油中的部分放电(PD)的存在是怀疑的,因为击穿和初始水平非常接近。这证实了目前接受的事实:[1] PD发生在油中。在击穿过程中,通常作为初始过程的一部分接受“气泡”或“腔”的形成。当气泡达到“临界尺寸”时,出现放电[2]。当发生这种放电时,可以示出气泡可以达到导致第二放电的尺寸,这增加到击穿。如果它突发成较小的尺寸放电停止[3,4]。这非常低。