A Parallel Resonance Investigation in Stockholm's Future Cablified Transmission Grid: A Prospective Study on Transformer Energization

机译:斯德哥尔摩未来无限制传输网格的并行共振调查:变压器通电的前瞻性研究

获取原文

摘要

As part of a planned grid expansion in the Stockholm region it is expected that a significant amount of HV cables will be installed. Due to concerns for possible low-order resonances, caused by the large amount of cables, studies have been conducted to investigate the risk of temporary overvoltages following transformer energization in the future power system around Stockholm. It was found that the system has a first parallel resonance point close to 150 Hz which is a possible concern when energizing transformers. However, time domain simulations showed that, despite several worst-case assumptions, the risk of severe overvoltages in the studied cases is small, especially when considering the inclusion of loads.
机译:作为斯德哥尔摩区域计划网格膨胀的一部分,预计将安装大量的高压电缆。由于担心由大量电缆引起的可能低位共振,已经进行了研究,以研究在斯德哥尔摩周围的未来电力系统中变压器通电后临时过电压的风险。结果发现,该系统具有接近150 Hz的第一并联谐振点,这是激励变压器时可能的问题。然而,时间域模拟表明,尽管有几种最坏的假设,所研究的情况下严重过电压的风险很小,特别是在考虑载荷时。