摘要

In this article authors considering the issue of the power transformer’s windstand capability from the point of view, that wasn’t mentioned before. Authors compare windstand forces between short circuit and turning on no-load mode operating modes. The risk of damage of a winding by an inrush current, that occurs during the process of turning on no-load mode was assessed. The values of the inrush current and the short circuit currents were calculated for ORTS417000/750/24/24 transformer. Conclusions about the possibility of reaching a value close to the short - circuit current by inrush currents in certain situations are made. Calculations of magnetic fields and electrodynamic forces in the transformer for these operating modes are performed. Conclusions about the influence of the operating mode of the transformer on the value and place of application of electrodynamic forces are made. It is concluded that it is necessary to take into account the process of turning on noload mode when checking the electrodynamic windstand of transformers.
机译:在本文中,提交人们考虑到了从特色视角下发出了电力变压器的朝向能力的问题。作者比较短路之间的挡脉部,打开无负载模式操作模式。评估在接通空载模式过程中发生浪涌电流绕组的损坏的风险被评估。为ORTS417000 / 750/24/24变压器计算了浪涌电流和短路电流的值。结论,制作了通过某些情况下涌入浪涌电流接近短路电流的可能性的结论。进行这些操作模式的变压器中的磁场和电动力的计算。关于变压器的操作模式对电动力力的价值和应用地点的结论。结论是,在检查变压器的电动挡板时,有必要考虑到诺纳载模式的过程。