Covering peak loads with phase change materials in a geothermal and desiccant assisted air conditioning system

机译:覆盖地热和干燥剂辅助空调系统中的相变材料覆盖峰值载荷

获取原文

摘要

In a geothermal and desiccant assisted air conditioning system at Hamburg University of Technologycovering thermal peak loads by means of phase change materials (PCM) is investigated. In theconsequence of high ambient temperatures the cooling power of the soil can be exceeded and abackup system is necessary. In this study experimental data of a backup system consisting of PCMencapsulated in plates and placed in a rack is presented. A computer case fan is used to induce avolume flow through the PCM rack. Results show that the PCM rack is able to locally focus coolingoperation and as a result improve thermal comfort perception. An air temperature reduction ofapproximately 0.7 – 0.9 ℃ at an average cooling power of 26.58 W can be achieved. The COPaccounts for 6.65 with a corresponding electricity consumption of 4 W.
机译:在汉堡理工大学的地热和干燥剂辅助空调系统中通过研究通过相变材料(PCM)覆盖热峰值负荷。在里面高环境温度的结果可以超过土壤的冷却功率和一个备份系统是必要的。在本研究中,由PCM组成的备份系统的实验数据封装在板中并置于机架中。电脑壳风扇用于诱导音量流过PCM机架。结果表明,PCM机架能够局部焦点冷却操作,结果提高了热舒适感。空气温度降低可以实现约0.7℃的平均冷却功率26.58W。 cop占6.65,相应的电力消耗为4 W.