首页> 外文会议>International Forum on Electrical Engineering and Automation >Parameter Matching of DC Reactor and DC Circuit Breaker in Multi-terminal DC Distribution System
【24h】

Parameter Matching of DC Reactor and DC Circuit Breaker in Multi-terminal DC Distribution System

机译:多终端直流分配系统中直流抗液器和直流断路器的参数匹配

获取原文

摘要

Compared with the two-terminal distribution system, the multi-terminal system has the characteristics of high flexibility and reliability. However, the fault analysis and protection are more complex. This paper analyzes the generation mechanism of short-circuit current of half-bridge converter, calculates the fault current of three-terminal ring network, and proposes a parameter matching method of DC circuit breaker and current limiting reactor which lays a foundation for the protection of the DC line. A three-terminal DC loop network is built in MATLAB to verify the correction of the parameter calculation method by simulation. The DC circuit breaker cooperated with the current limiter can isolate the fault within the breaking capacity, and the system voltage can recover rapidly after the fault is isolated.
机译:与双终端配电系统相比,多终端系统具有高灵活性和可靠性的特点。但是,故障分析和保护更复杂。本文分析了半桥转换器的短路电流的产生机制,计算了三端环网的故障电流,提出了直流断路器和限流反应器的参数匹配方法,为保护奠定了基础直流线。在MATLAB中内置了三端直流循环网络,以验证通过仿真校正参数计算方法。与电流限制器配合的直流断路器可以在断开容量内隔离故障,并且在隔离故障后系统电压可以快速恢复。