Current Order Based Recovery Strategy for Successive Commutation Failure Inhibition in Multi-infeed HVDC Systems

机译:多进料HVDC系统中连续换向故障抑制的基于流的恢复策略

获取原文

摘要

Commutation failure (CF) of one dc system may lead to the successive CF of the adjacent dc system due to the close electrical distance and reactive power interaction in multi-infeed HVDC systems, resulting in serious regional power loss. In order to effectively inhibit the successive CF and realize the orderly recovery, a coordinated recovery strategy based on additional current order is proposed in this paper. In this strategy, voltage at ac busbar of the inverter is used as a criterion of reactive power margin, and the corresponding additional current order is calculated according to the judgement of reactive power margin. Considering different strength of dc systems, the multi-infeed short circuit ratio (MISCR) is utilized to calculate the proportionality factor for current order correction. Finally, by the superposition of voltage dependent current order limiter (VDCOL) and the additional current order, the current setting value of rectifier side is obtained to realize the incremental recovery. The test system is built in PSCAD/EMTDC, and the simulation result verify the validation of the proposed strategy.
机译:由于多进样HVDC系统中的密切电距离和无功功率相互作用,一个直流系统的换向故障(CF)可能导致相邻DC系统的连续CF,导致严重的区域功率损失。为了有效抑制连续的CF并实现有序恢复,本文提出了一种基于额外电流顺序的协调回收策略。在该策略中,逆变器的AC汇流条的电压用作无功功率余量的标准,并且根据无功功率裕度的判断来计算相应的附加电流顺序。考虑到DC系统的不同强度,利用多进给短路比(MISCR)来计算电流顺序校正的比例因子。最后,通过叠加电压相关电流阶限制器(VDCOL)和附加电流顺序,获得整流侧的电流设定值以实现增量恢复。测试系统内置于PSCAD / EMTDC,仿真结果验证了拟议策略的验证。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号