A Novel Control Strategy for Suppression of HVDC Subsequent Commutation Failure

机译:一种抑制HVDC后续换向故障的新型控制策略

获取原文

摘要

In the case of AC failures at the receiving end of the HVDC system, commutation failures are likely to occur, which may cause the converter station to lock up and seriously threaten the safety of the power grid. In order to suppress the subsequent commutation failure of HVDC, this paper studies the response of the electrical quantity and the control quantity when the system is in the recovery process. The DC current and the firing angle are not coordinated, resulting in insufficient commutation voltage-time area margin and the inability to complete the commutation process. For this reason, this paper proposes a subsequent commutation failure suppression strategy. By limiting the DC current when the firing angle overshoots, the subsequent commutation failure is suppressed to achieve effective recovery of the DC system. The CIGRE standard test model is used in EMTDC to test and verify the proposed theory.
机译:在HVDC系统的接收端的AC故障的情况下,可能发生换向故障,这可能导致转换器站锁定并严重威胁到电网的安全性。为了抑制HVDC后续换向故障,本文研究了系统处于恢复过程时电量和控制量的响应。不协调DC电流和烧制角,导致换向电压时面积余量不足,无法完成换向过程。出于这个原因,本文提出了后续换向失败抑制策略。通过限制DC电流当发射角过冲时,随后的换向故障被抑制以实现DC系统的有效恢复。 CIGRE标准测试模型用于EMTDC进行测试和验证所提出的理论。