首页> 外文会议>IEEE International Conference on Dielectrics >Frequency Analysis and Recurrent Plot of the Leakage Current to Monitoring the Insulator Surface State
【24h】

Frequency Analysis and Recurrent Plot of the Leakage Current to Monitoring the Insulator Surface State

机译:漏电流的频率分析和复发曲线监测绝缘子表面状态

获取原文

摘要

This work is devoted to study the insulator behavior in the desert region. The purpose of our study is to examine the effect of the increasing of the sand quantity uniformly and non-uniformly distributed with different polluted layer widths on the insulator surface behavior. The leakage current (LC) signal represents an important source of information. The Fast Fourier Transform (FFT) technique is used to extract the harmonic components of the LC for each configuration of the pollution. The fundamental component and the odd harmonic components can be well correlated with the insulator surface state. We also used the recurrent plot (RP) technique applied on the LC waveforms. We based on the variation of the RP maps to monitoring the insulators surface state.
机译:这项工作致力于研究沙漠地区的绝缘子行为。我们研究的目的是检查均匀和不均匀分布在绝缘体表面行为上的不同污染层宽度均匀和不均匀分布的效果。漏电流(LC)信号代表了一个重要信息来源。快速傅里叶变换(FFT)技术用于提取污染的每种配置的LC的谐波分量。基本部件和奇谐波分量可以与绝缘体表面状态良好相关。我们还使用了在LC波形上施加的复制图(RP)技术。我们基于RP地图的变化来监测绝缘子表面状态。