Polymeric insulators have shown tremendous growth in their application and are under continuous upgradation since their inception. Insulators undergo several stresses as they are exposed to outer environment and being organic in nature, polymeric insulators degrade because of UV, corona, acid attacks, mechanical and electrical stresses etc. This paper presents the Fourier Transform Infrared (FTIR) spectrum analysis of the failed 220 kV silicone rubber polymeric insulators. The occurrence of different physico-chemical changes in the different shed positions of the failed insulators is studied. The preliminary investigation showed the loss of Alumina Tri Hydrate (ATH) filler from the failed insulator samples. Retention of hydrophobicity have also been reported in the present work.
机译:聚合物绝缘体在其申请中表现出巨大的增长,并且自成立以来持续升级。绝缘体经历了几种压力,因为它们暴露于外部环境并且是有机的,聚合物绝缘体因UV,电晕,酸攻击,机械和电力应力等而降解。本文介绍了失败的傅里叶变换红外(FTIR)谱分析220 kV硅橡胶聚合物绝缘体。研究了失败绝缘体的不同棚位置不同的物理化学变化的发生。初步调查显示,氧化铝三水合物(Ath)填料的损失来自失败的绝缘体样品。目前的工作中还报告了疏水性的保留。