首页> 外文会议>High Voltage Engineering and Application-ICHVE, 2008 International Conference on >Study of the Influences on Soil Resistivity Caused by HVDC Mono-polar Operation
【24h】

Study of the Influences on Soil Resistivity Caused by HVDC Mono-polar Operation

机译:高压直流输电单极运行对土壤电阻率的影响研究

获取原文

摘要

UHVDC transmission system has many advantages, such as transferring large amounts of electrical power over long distances. It plays an important role in the west to east power transmission project. The ground electrode of UHVDC was working in several kA currents for long-term when it works in mono-polar operation. And there is high temperature of the soil around the ground electrode in that time. The normal operation of ground electrode can be impacted by the soil resistivity around it. Porous media model is introduced in this paper. Based on this model, impact of temperature on soil resistivity is presented. And the relationship of current density and soil resistivity is analyzed. Then, an experiment was done to validate it.
机译:特高压直流输电系统具有许多优点,例如可以远距离传输大量电能。在西电东送工程中发挥着重要作用。 UHVDC的接地电极在单极工作模式下可以长期工作在数kA的电流下。那时接地电极周围的土壤温度很高。接地电极的正常运行会受到其周围土壤电阻率的影响。本文介绍了多孔介质模型。基于该模型,提出了温度对土壤电阻率的影响。并分析了电流密度与土壤电阻率的关系。然后,做了一个实验来验证它。