首页> 外文会议>空気調和·衛生工学会大会 >Evaluation of ISO 7243 and Other Indices Relating to Application of Mist Evaporation Cooling in Hot Environments to Reduce Heat Stress on Workers
【24h】

Evaluation of ISO 7243 and Other Indices Relating to Application of Mist Evaporation Cooling in Hot Environments to Reduce Heat Stress on Workers

机译:对ISO 7243的评估以及与在热环境中应用雾化蒸发冷却以减少工人的热应力有关的其他指标

获取原文

摘要

Mist evaporation cooling could be a low-cost means to reduce heat stress on workers in hot environments where standard air conditioning is impractical. ISO7243 and JISZ8504 standards, which regulate the rest rate for such workers, are based on the natural Wet Bulb Globe Temperature(WBGTn). Mist evaporation takes place at nearly-constant wet bulb temperature. Calculations confirm mist cooling would yield almost no change in WBGTn. Indices based on thermal load on the body including PMV, ET* and 2-node Pierce model all show mist should yield improvement for typical workers. This suggests the standard is not suited to correctly evaluate mist cooling.
机译:薄雾蒸发冷却可能是一种低成本的方法,可以减少在标准空调不可行的炎热环境中对工人的热压力。规范此类工人的休息率的ISO7243和JISZ8504标准基于自然的湿球温度(WBGTn)。雾气蒸发发生在接近恒定的湿球温度下。计算结果证实,薄雾冷却不会使WBGTn产生任何变化。基于人体的热负荷的指数(包括PMV,ET *和2节点Pierce模型)均显示出雾气对于典型工人而言应该会有所改善。这表明该标准不适合正确评估雾气冷却。