首页> 外文会议>Industrial Electronics (IECON), 2008 34th Annual Conference of IEEE >A new control method of a current balancer in single-phase three-wire secondary distribution systems using the correlation and cross-correlation coefficients
【24h】

A new control method of a current balancer in single-phase three-wire secondary distribution systems using the correlation and cross-correlation coefficients

机译:利用相关系数和互相关系数的单相三线二次配电系统中电流平衡器的新控制方法

获取原文

摘要

This paper proposes a new control method of a current balancer for single-phase three-wire secondary distribution systems using the correlation and cross-correlation coefficients to reduce the capacity of the three-leg PWM inverter, which performs the current balancer. The components correlative and cross-correlative to the primary side voltage waveform, which correspond to the active and reactive currents, are calculated from the detected load currents on each feeder. Then the reactive and unbalanced-active currents are compensated on the source side. The balanced source currents with the power factor of 0.9 are obtained in each feeder. This imperfect compensation of the reactive power reduces the capacity of both the three-leg PWM inverter and dc capacitor. The basic principle of the proposed method is discussed in detail, and then confirmed by digital computer simulation. A proto-type experimental system is constructed and tested. Experimental results demonstrate that the balanced source currents with the power factor of 0.9 are obtained in spite of unbalanced load currents reducing the capacity of the three-leg PWM inverter.
机译:提出了一种利用相关系数和互相关系数来减小三脚PWM逆变器容量的单相三线二次配电系统电流平衡器的新控制方法。根据每个馈线上检测到的负载电流,计算出与初级侧电压波形相关且互相关的分量,分别对应于有功和无功电流。然后,在源侧补偿无功和不平衡有功电流。在每个馈线中获得功率因数为0.9的平衡电源电流。对无功功率的不完美补偿会降低三脚PWM逆变器和直流电容器的容量。详细讨论了该方法的基本原理,然后通过数字计算机仿真对其进行了确认。构建并测试了原型实验系统。实验结果表明,尽管不平衡负载电流降低了三脚PWM逆变器的容量,但仍获得了功率因数为0.9的平衡电源电流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号