Arcing in SF6-MV-switchgear. Pressure rise in equipmentroom

机译:SF 6 -MV-开关设备中的电弧。设备压力上升房间

获取原文

摘要

The authors discuss fault arcing in a MV transformer substationwith a comparison between SF6 and air insulated switchgear.The work is concentrated on the overpressure (pressure rise) in thecable and transformer compartments. There is reason to believe thatpressure rise should be higher with SF6 compared to air. Fullscale tests have shown that the maximum pressure rise is about equal forSF6 and air, but with a significantly longer duration of thepressure rise in the case of SF6. It has been found difficultto simulate practical conditions by small scale model tests
机译:作者讨论了MV变电站中的故障电弧 在SF 6 和空气绝缘开关设备之间进行了比较。 这项工作集中在超压(压力上升)上 电缆和变压器隔间。有理由相信 与空气相比,压力升高应高于SF 6 。满的 规模测试表明,最大压力升高约为相等 SF 6 和空气,但具有明显更长的持续时间 SF 6 的情况下的压力升高。它被发现很难 通过小规模模型测试模拟实际情况