首页> 外文会议>IEEE Power and Energy Society Innovative Smart Grid Technologies Conference >Local detection of PMU measurement errors using dynamic state estimators
【24h】

Local detection of PMU measurement errors using dynamic state estimators

机译:使用动态状态估计器本地检测PMU测量误差

获取原文

摘要

This paper proposes the use of a couple of local PMUs and associated dynamic state estimators in order to detect and remove bad data in PMU measurements. Distinguishing features of the proposed approach is that it facilitates detection of bad-data in local PMU measurements without requiring a system-wide state estimator. The proposed approach relies on a performance evaluation technique which computes the probability density function (pdf) of the residuals provided by a dynamic state estimator. In the proposed approach it is assumed that there are at least two local PMUs that provide measurements to the dynamic state estimators of a synchronous generator. The proposed approach is implemented using a two-axis model of a synchronous generator with IEEE-Type 1 exciter. The performance of the proposed approach is investigated in the presence of bad-data associated with the measurements provided by the PMUs.
机译:本文提出了使用几个本地PMU和相关的动态状态估计,以检测和删除PMU测量中的不良数据。所提出的方法的显着特征在于它有助于在局部PMU测量中检测错误数据,而无需系统范围的状态估计器。所提出的方法依赖于一种性能评估技术,其计算由动态状态估计器提供的残差的概率密度函数(PDF)。在所提出的方法中,假设存在至少两个局部PMU,其为同步发电机的动态状态估计提供测量。使用具有IEEE-Type 1激励器的同步发生器的双轴模型来实现所提出的方法。在与由PMU提供的测量相关的错误数据存在下,研究了所提出的方法的性能。