首页> 外文会议>IEEE Power and Energy Society Innovative Smart Grid Technologies Conference >Experimental evaluation of grid support enabled PV inverter response to abnormal grid conditions
【24h】

Experimental evaluation of grid support enabled PV inverter response to abnormal grid conditions

机译:电网支持的光伏逆变器对异常电网条件的响应的实验评估

获取原文

摘要

As revised interconnection standards for grid-tied photovoltaic (PV) inverters address new advanced grid support functions (GSFs), there is increasing interest in inverter performance in the case of abnormal grid conditions. The growth of GSF-enabled inverters has outpaced the industry standards that define their operation, although recently published updates to UL1741 Supplement SA define test conditions for GSFs such as volt-var control, frequency-watt control, and voltage/frequency ride-through, among others. This paper describes the results of a comparative experimental evaluation on four commercially available, three-phase PV inverters in the 24.0-39.8 kVA power range on their GSF capability and its effect on abnormal grid condition response. The evaluation examined the impact particular GSF implementations have on run-on times during islanding conditions, peak voltages in load rejection overvoltage scenarios, and peak currents during single-phase and three-phase fault events for individual inverters. Testing results indicated a wide variance in the performance of GSF enabled inverters to various test cases.
机译:作为网格连接光伏(PV)逆变器的修订互连标准地址新的高级网格支持功能(GSFS),在网格条件异常的情况下,对变频性能的兴趣越来越令人兴趣。支持GSF的逆变器的增长超越了定义其操作的行业标准,尽管最近发布了UL1741补充SA的更新,可定义GSF的测试条件,如Volt-Val控制,频率 - 瓦控制和电压/频率骑行,其中。本文介绍了在其GSF能力的24.0-39.8 kVA功率范围内进行四种商业三相PV逆变器对比较实验评价的结果及其对异常网格条件反应的影响。评估检测了在岛屿条件期间在运行时的冲击特定GSF实现,负载抑制过压场景中的峰值电压,单相和三相故障事件中的峰值电流为个体逆变器。测试结果表明,GSF使能逆变器的性能方差差异很大。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号