首页> 外文会议>放電研究会;開閉保護研究会;高電圧研究会 >Detection of Partial Discharges in Electric Power Equipment using an Electromagnetic Wave Sensor
【24h】

Detection of Partial Discharges in Electric Power Equipment using an Electromagnetic Wave Sensor

机译:使用电磁波传感器检测电力设备中的局部放电

获取原文

摘要

To diagnose electric power apparatus under operation, to detect partial discharge (PD) which refers predictive phenomenon on insulation deterioration of the power apparatus is useful. An electromagnetic (EM) wave sensor technique is widely accepted for the detection of PDs. We installed a PD source in a 6.6 kV transformer tank. EM waves owing to the PDs were measured from the outside of the tank by an EM sensor. As the result, we successfully detected PDs with the magnitude of more than 10 pC and confirmed a linearity between the magnitude of EM signal and electrical charge of PD.
机译:为了诊断运行中的电力设备,检测与电力设备的绝缘劣化有关的预测现象的局部放电(PD)是有用的。电磁(EM)波传感器技术已被广泛用于PD的检测。我们在6.6 kV变压器油箱中安装了一个PD源。由PD产生的EM波是由EM传感器从储罐外部测量的。结果,我们成功地检测到大小超过10 pC的PD,并确认了EM信号的大小与PD电荷之间的线性关系。