Switching Transients at Cable Transmission System

机译:电缆传输系统的瞬变

获取原文

摘要

There are many transient phenomena at circuit breaker switching. In the past, transient recovery voltage (TRV) for the circuit breaker at overhead transmission line system is mainly investigated. The TRV at cable transmission system is few investigated because there was few the cable transmission system. In this paper, The TRVs at breaker terminal fault (BTF) and short line fault (SLF) for cable transmission are shown. 33kV and 11kV cable transmission system with 10km length respectively are modelled. The calculated TRV parameters are compared with the IEC standard.
机译:断路器开关时有许多瞬态现象。过去,主要研究架空传输线系统中断路器的瞬态恢复电压(TRV)。由于电缆传输系统很少,因此很少研究电缆传输系统的TRV。本文显示了用于电缆传输的断路器端子故障(BTF)和短线故障(SLF)处的TRV。分别模拟了33kV和11kV长度为10km的电缆传输系统。将计算出的TRV参数与IEC标准进行比较。