首页> 外文会议>International Conference on Probabilistic Methods Applied to Power Systems >Probabilistic assessment of impacts of real-time line ratings on distribution networks
【24h】

Probabilistic assessment of impacts of real-time line ratings on distribution networks

机译:实时线路额定值对配电网络影响的概率评估

获取原文

摘要

Underground cabling systems which includes cables and ducts play a vital role in the planning and assessment of electro-thermal coordination that will incorporate smart energy transmission and utilize the prevailing weather conditions in implementing future smart distribution systems. This paper investigates the effects of increased adequacy through real-time line thermal ratings on network losses and risk of ageing. The analysis is performed on a range of underground cable duct installation methods in a distribution network. The paper proposes a new technique of assessing the reliability of distribution systems when real-time line rating is implemented on power cables considering the ducting methods and accounting for the reliability risks of cable ageing. Probabilistic assessments on nine different ducting installations for a buried 22kV XLPE cable showed that an oil pressure type cable ducting has the lowest risk of asset ageing when real-time line rating is implemented on the network.
机译:地下电缆系统(包括电缆和导管)在电热协调的规划和评估中起着至关重要的作用,它将整合智能能源传输并利用当前的天气条件来实施未来的智能配电系统。本文研究了通过实时线路热额定值提高充足性对网络损耗和老化风险的影响。该分析是在配电网络中对各种地下电缆管道安装方法进行的。本文提出了一种新技术,用于评估在电力电缆上实现实时线路额定值时配电系统的可靠性,该技术应考虑管道方法并考虑电缆老化的可靠性风险。对22kV XLPE埋入式电缆的9种不同管道安装进行的概率评估表明,当在网络上实施实时线路额定值时,油压式电缆管道的资产老化风险最低。