This paper presents the performance evaluation of a two-terminal fault location method based on aerial and ground mode traveling waves applied to the Madeira River Bipole 1. The above mentioned High Voltage Direct Current (HVDC) system was modeled and simulated using the Alternative Transients Program (ATP). The method accuracy was evaluated through pole-to-ground fault scenarios for different fault positions and fault resistances. The obtained results reveal that the evaluated fault location method presents errors smaller than a conventional tower span (≈ 300 m). Also, in cases of uncertainties in line parameters, the method kept the same performance, since it is independent of the propagation velocities and line length.
机译:本文介绍了基于航拍和地面模式行波应用于马德拉河双极1的两端故障定位方法的性能评估。使用替代暂态程序对上述高压直流(HVDC)系统进行了建模和仿真(ATP)。通过针对不同故障位置和故障电阻的极地故障场景评估了方法的准确性。所得结果表明,所评估的故障定位方法所产生的误差小于常规塔架跨度(≈300 m)。另外,在线路参数不确定的情况下,该方法保持相同的性能,因为它与传播速度和线路长度无关。