This paper presents a new test methodology for verifying the interoperability and application performance of PMUs and PMU-enabled IEDs at the device and system level. Two types of tests are defined to evaluate the performance of synchrophasor devices from two different aspects: design and application. The interoperability between PMUs, time synchronization options, and phasor data concentrators (PDCs) can be verified by design test methodology. A fault location algorithm using two-end synchronized measurements is used to evaluate the application performance. A reference PMU algorithm and synchrophasor system test set-up have been developed to perform the tests. Nine commercial PMUs and four GPS receivers with different synchronization options are selected to perform the tests. The test results are summarized at the end.
机译:本文提出了一种新的测试方法,用于在设备和系统级别上验证PMU和启用PMU的IED的互操作性和应用性能。定义了两种类型的测试以从两个不同方面评估同步相量设备的性能:设计和应用。可以通过设计测试方法来验证PMU,时间同步选项和相量数据集中器(PDC)之间的互操作性。使用两端同步测量的故障定位算法用于评估应用程序性能。已经开发了参考PMU算法和同步相量系统测试设置来执行测试。选择了九个商用PMU和四个具有不同同步选项的GPS接收器来执行测试。最后总结了测试结果。