首页> 外文会议>Industrial amp; Commercial Power Systems Technical Conference, 1999 IEEE. >A new approach for transformer ground differential protection
【24h】

A new approach for transformer ground differential protection

机译:变压器接地差动保护的新方法

获取原文

摘要

Existing electromechanical ground differential protection relaysare impaired in the event of CT saturation. They might trip when thefault is external (or not trip when the fault is internal) unless theconfiguration and settings are designed very carefully. In addition,inrush effects can also cause wrong protection behavior. Simulations andfield observations have revealed that the phase angle difference betweenthe ground current and zero sequence current, in combination with theratio of their magnitudes, can be used to identify precisely atransformer ground fault. These observations were used for thedevelopment of a new numerical transformer differential protectiverelay. Simulations and test results have shown that the new solutioncorrectly detects a wider range of phenomena that would indicate aninternal fault, while remaining able to not trip in the event of anexternal fault
机译:现有的机电接地差动保护继电器 CT饱和时受损。他们可能会在 故障是外部的(或故障是内部的,则不跳闸),除非 配置和设置的设计非常仔细。此外, 涌入效应还会导致错误的保护行为。模拟和 现场观察发现,相间的相角差 接地电流和零序电流,以及 它们的大小之比,可以用来精确识别 变压器接地故障。这些观察结果用于 新型数值变压器差动保护的开发 中继。仿真和测试结果表明,该新解决方案 正确检测范围更广的现象,这些现象表明 内部故障,但在发生故障时仍然能够跳闸 外部故障