The Constructing of Backup Protections of Overhead Lines Taking into Account the Effect of the Magnetizing Current of the Power Transformers

机译:考虑电力变压器励磁电流影响的架空线路后备保护装置的构建

获取原文

摘要

The authors refined the values of phase currents and their harmonic components to calculate the backup protection parameters of overhead lines with branch transformer substations in the regime of turning them on at idle. Despite the significant attenuation of the magnetizing current for the operation moment of the indicated protections, which usually operate with significant time delays, it should be noted that these values are comparable with the operation currents selected on the requirement basis of high sensitivity to fault behind low-power transformers. Analytical dependences of currents on the initial state of transformers and parameters of the electric network are obtained. This allows us to reasonably calculate backup protection settings of overhead lines with branch and intermediate substations, which often allows us to provide the required sensitivity for short three-phase faults on the low voltage side of low-power transformers.
机译:作者细化了相电流及其谐波分量的值,以计算分支变压器变电站在闲置时将其架空的架空线路的后备保护参数。尽管在所示保护的工作时间内励磁电流已显着衰减,通常在相当长的时间延迟内运行,但应注意,这些值可与根据对故障的敏感性高而要求低而要求的选择的工作电流相媲美。 -电力变压器。获得了电流对变压器初始状态和电网参数的分析依赖性。这使我们能够合理地计算分支和中间变电站的架空线的备用保护设置,这通常使我们能够为低功率变压器的低压侧的短时三相故障提供所需的灵敏度。