Faulty Phase and Faulty Line Selection Method Based on Three-Phase Transient Current

机译:基于三相暂态电流的故障相和故障线选择方法

获取原文

摘要

The neutral point of distribution network is usually ungrounded or grounded through arc suppression coil in China. When a single-phase-to-ground fault occurs, the fault current is small, which brings difficulties to fault diagnosis. A method of faulty phase and faulty line selection for single-phase-to-ground fault based on three-phase transient current is proposed. Firstly, the faulty phase is identified by the difference in the transient current between the faulty phase and the healthy phase. Then, the transient current of each line is decomposed and reconstructed by the wavelet packet, and the ratio of the transient current energy in the selected frequency band of each line is calculated to identify the faulty line. Finally, several groups of artificial grounding experiments have been carried out in a 10kV real type test field to verify the correctness of the proposed faulty phase selection and faulty line selection method.
机译:在中国,配电网的中性点通常不接地或通过消弧线圈接地。当发生单相接地故障时,故障电流很小,给故障诊断带来困难。提出了一种基于三相暂态电流的单相接地故障相线和故障选线方法。首先,通过故障相与健康相之间的瞬态电流差异来识别故障相。然后,通过小波包分解和重构每条线路的瞬态电流,并计算每条线路的选定频带中的瞬态电流能量之比,以识别故障线路。最后,在10kV实型测试场中进行了几组人工接地实验,以验证所提出的故障相选择和故障线路选择方法的正确性。